Color:Green
Model: There are many model to choose from. Please check the details.
Model Number : TORD4B-63
Type : Earth Leakage
Rated voltage : 230V/400V
Residual Current characteristic : B type
Rated residual operating current : 30 mA
Breaking capacity : 10 KA
Model : Electromagnetic Type
Rated frequency : 50/60Hz
Electro-mechanical endurance : More than 15000 cycles
-
-
General
This is B Type Residual Current Circuit Breaker
-
-
Tip: Please noted the input MUST from TOP side, or will damage the product.
-
The default rated voltage of the product is 230V, (110V needs to be customized, please contact customer service)
Type B RCCBs, in addition to normal AC, can detect high frequency AC and pure DC earth leakage currents. Reducing the risk of fire and/or electrocution through automatic disconnection of the electrical supply relies on the selection of the correct type of RCCB.
View ‘B’ Type
-
-
EV & PV installationsFrequency convertersUPS installationsHigh-frequency power convertersBuilding site power supply cabinets1.1 Function
-
Control electric circuits.Protect people against indirect contacts and additionalprotection against direct contacts.Protect installations against fire hazard due to insulation faults.Residual current circuit breakers are used in housing, tertiarysector and industry
-
1.2 SelectionDetectable wave formB classTripping is ensured for sinusoidal AC residual currents pulsed DCresidual currents,alternatingresidual sinusoidal currents up to1000Hz, pulsating direct residualcurrents and for smooth directresidual currents, whether applied suddenly or increasing slowly.Tripping sensitivity30mA -additional protection against direct contact.Tripping timeInstantaneous
It ensures instantaneous tripping (without time- delay).